Example: Error Stop using MC_Stop cannot be Aborted

MC_Halt and MC_Stop are both used to bring an axis to a Standstill but
MC_Stop is used when an abnormal situation occurs.

Motion Axis and
Parameters

The following state diagram illustrates the behavior of the axis at a high level
when multiple motion control function blocks are activated. The basic rule is that
motion commands are always taken sequentially, even if the controller has the
capability of real parallel processing. These commands act on the axis’ state
diagram.

The axis is always in one of the defined states (see diagram below). Any motion
command is a transition that changes the state of the axis and, as a consequence,
modifies the way the current motion is computed.

TIP

MC_Stop can abort other motion function blocks but can never be
aborted itself.

TIP

MC_Stop goes to the Stopping state and normal operation cannot
resume.

V

elocit

y

Time

MC_Stop Execute

Busy

Motion function block Execute

This command is ignored.