Schematic – using ansi/csa symbols), Schematic (using ansi/csa symbols) – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 34

Advertising
background image

20

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Chapter 2 About Your Controller

Schematic – Using ANSI/CSA Symbols)

Emergency-stop
push button

230V AC

Operation of either of these contacts will
remove power from the external I/O
circuits, stopping machine motion.

Fuse

MCR

Fuse

MCR

MCR

MCR

Stop

Start

Line Terminals: Connect to terminals of power
supply

Line Terminals: Connect to 24V DC terminals of
power supply.

230V AC
output
circuits

Disconnect

Isolation
Transformer

115V AC or
230V AC
I/O circuits

L1

L2

Master Control Relay (MCR)
Cat. No. 700-PK400A1

Suppressor
Cat. No. 700-N24

(Lo)

(Hi)

DC Power Supply. Use
NEC Class 2 for UL
Listing

.

X1

X2

115V AC or
230V AC

_

+

MCR

24 V DC
I/O
circuits

Suppr.

Overtravel
limit switch

44565

Advertising
This manual is related to the following products: