Micro850 24-point controllers – Rockwell Automation 2080-LC50 Micro830 and Micro850 Programmable Controllers User Manual User Manual

Page 182

Advertising
background image

166

Rockwell Automation Publication 2080-UM002F-EN-E - December 2013

Appendix A Specifications

Micro850 24-Point Controllers

General Specifications – 2080-LC50-24AWB, 2080-LC50-24QWB, 2080-LC50-24QVB, 2080-LC50-24QBB

Attribute

2080-LC50-24AWB

2080-LC50-24QWB

2080-LC50-24QVB

2080-LC50-24QBB

Number of I/O

24 (14 inputs, 10 outputs)

Dimensions
HxWxD

90 x 158 x 80 mm
(3.54 x 6.22 x 3.15 in.)

Shipping weight, approx.

0.423 kg (0.933 lb)

Wire size

0.2…2.5 mm

2

(24…12 AWG) solid copper wire or

0.2…2.5 mm

2

(24…12 AWG) stranded copper wire

rated @ 90 °C (194 °F ) insulation max

Wiring category

(1)

2 – on signal ports
2 – on power ports
2 – on communication ports

Wire type

Use Copper Conductors only

Terminal screw torque

0.4…0.5 Nm (3.5…4.4 lb-in.) using a 0.6 x 3.5 mm flat-blade screwdriver.
(Note: Use a handheld screwdriver to hold down the screws at the side.)

Input circuit type

12/24V sink/source (standard)
24V sink/source (high-speed)

Output circuit type

Relay

24V DC sink (standard
and high-speed)

24V DC source (standard
and high-speed)

Power consumption

28 W

Power supply voltage range

20.4…26.4V DC Class 2

I/O rating

Input 120V AC 16 mA
Output 2 A, 240V AC,
2A, 24V DC

Input 24V, 8.8 mA
Output 2 A, 240V AC
2A, 24V DC

Input 24V, 8.8 mA
Output 24V DC, Class 2, 1 A per point (Surrounding
air temperature 30 °C)
24V DC, Class 2, 0.3 A per point (Surrounding air
temperature 65 °C)

Isolation voltage

250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to Outputs.
Type tested for 60 s @ 3250V
DC Output to Aux and Network,
Inputs to Outputs
150V (continuous), Reinforced
Insulation Type, Input to Aux
and Network.
Type tested for 60 s @ 1950V
DC Input to Aux and Network

250V (continuous), Reinforced
Insulation Type, Output to Aux
and Network, Inputs to
Outputs.
Type tested for 60 s @ 3250V
DC Output to Aux and Network,
Inputs to Outputs.
50V (continuous), Reinforced
Insulation Type, Input to Aux
and Network
Type tested for 60 s @ 720V
DC, Input to Aux and Network

50V (continuous), Reinforced Insulation Type, I/O to
Aux and Network, Inputs to Outputs.
Type tested for 60 s @ 720 V DC, I/O to Aux and
Network, Inputs to Outputs.

Pilot duty rating

C300, R150

Insulation stripping length

7 mm (0.28 in.)

Enclosure type rating

Meets IP20

North American temp code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication

1770-4.1

.

Advertising
This manual is related to the following products: