User Interrupts Appendix D

This parameter is configured with the programming device and cannot be
changed from the control program.

EII Function Status Information

EII Function status bits can be monitored either in the User Program, or in
Connected Components Workbench, in Debug mode.

EII User Interrupt Executing (EII0.EX)

The EX (User Interrupt Executing) bit is set whenever the EII mechanism
detects a valid input and the controller is scanning the EII POU. The EII
mechanism clears the EX bit when the controller completes its processing of the
EII subroutine.

The EII EX bit can be used in the control program as conditional logic to detect
if an EII interrupt is executing.

EII User Interrupt Enable (EII0.Enabled)

The Enabled (User Interrupt Enable) bit is used to indicate the EII enable or
disable status.

EII User Interrupt Lost (EII0.LS)

LS (User Interrupt Lost) is a status flag that represents an interrupt has been lost.
The controller can process 1 active and maintain up to 1 pending user interrupt
conditions before it sets the lost bit.

This bit is set by the controller. It is up to the control program to utilize or track,
the lost condition if necessary.

EII User Interrupt Pending (EII0.PE)

PE (User Interrupt Pending) is a status flag that represents an interrupt is
pending. This status bit can be monitored, or used for logic purposes, in the

Sub-Element Description

Data Format

User Program
Access

EX - User Interrupt Executing

binary (bit)

read only

Sub-Element Description

Data Format

User Program Access

Enabled - User Interrupt Enable

binary (bit)

read only

Sub-Element Description

Data Format

User Program Access

LS - User Interrupt Lost

binary (bit)

read/write

Sub-Element Description

Data Format

User Program Access

PE - User Interrupt Pending

binary (bit)

read only