Bc a – Kontron TIGH2U Carrier Grade Server User Manual

Page 90

Advertising
background image

TIGH2U Server—Server Component Replacements

Kontron Carrier Grade Server TIGH2U

Product Guide, rev.1.2

December 2009

90

5. Remove the TAM board. For instructions, see

Section 5.3.1, “Removing the TAM Board” on

page 84

.

6. Remove the PCI fan assembly. For instructions, see

Section 5.2.4, “Removing the PCI Fan

Assembly” on page 78

.

7. Remove the CPU fan assembly. For instructions, see

Section 5.2.1, “Removing the CPU Fan

Assembly” on page 75

.

8. Disconnect all of the cables connected to the SFP board:

— SAS backplane power cable
— All four fan power cables
— Two power input cables from the power distribution board
— Flex cable
— Intel

®

RAID Smart Battery cable, if the smart battery is installed

— Front serial port cable

Use

Section 35, “System Cable Routing” on page 53

as a reference for the connectors.

9. Open the bridge board connector latches. (

Figure 70

, “A”)

10. Lift the bridge board from the chassis (“B” and “C”)

Figure 70.

Removing the Bridge Board

TS000435

B

C

A

11. Remove the SFP board screw (

Figure 71

, “A”).

12. Remove the threaded TAM board standoff. (“B”)