Msi-9850, Set points, Driving 5v coil relays – Rice Lake MSI-9850 CellScale RF Digital Indicator - Operator Manual User Manual

Page 16: Driving externally powered coil relays

Advertising
background image

Page 16 MSI-9850 RF Remote Indicator • User Guide

MSI-9850

HANDHELD RF REMOTE INDICATOR for

C

ELL

S

CALE

®

9850 P3

Set Points Port

Pin 1- 5V Out

Pin 2 - SP2

Pin 3 - SP3

Pin 4 - SP5

or GND

Pin 5 - SP1

Set Points

BRN

WHT

BLUE

BLK

GREY

5Vdc

Snubber Diodes

not required

Driving 5V Coil Relays

Limit 150mA ea

max coil current

(or 500mA Total)

+

+

+

+

Pin 5 - SP4

PINK

+

Use of SP5

requires Jumper

JP6 positioned

1-2. JP6 is

defaulted to GND

and will turn on

any relay

connected to the

black wire when

the 9850 power

is turned on.

Insulate all unused wires.

9850 P3

Set Points Port

Pin 1- 5V Out

Pin 2 - SP2

Pin 3 - SP3

Pin 4 - GND

Pin 5 - SP1

Set Points

BRN (NC)

WHT

BLUE

BLK

GREY

5Vdc-25Vdc

Snubber Diodes

not required

Driving Externally Powered Coil Relays

Limit 150mA ea

max coil current

Pin 5 - SP4

PINK

Insulate Brn

Wire

Insulate all unused wires.

JP6 in default GND

Position (1-4)

Relay

Power

Source

+

+

+

+

+

Brown Provides a +5V source for driving relays or auxiliary devices. Fused with a self resetting Polyswitch

device. Maximum output current is 500mA total. This output is diode protected and not highly regu-

lated as the regulated voltage passes through a Schottky diode. Since V-forward of the Schottky diode

varies with current drain, the voltage will vary from a low of ~4.9V at 500mA to a high of 5.2V lightly

loaded.

White Open Drain Relay Driver, Set Point 2

Blue

Open Drain Relay Driver, Set Point 3

Black Defaults to circuit ground. Power return for the 5V supply. This line can be used to drive a master relay

that turns on when the 9850 turns on. Or by moving JP6 to poisition 1-2, provides an Open Drain Relay

Driver, Set Point 5

Grey Open Drain Relay Driver, Set Point 1

Pink

Open Drain Relay Driver, Set Point 4

With 5V relays, no other

power supply is required for

driving relay coils. Other

5V devices such as lamps or

alarms can also be powered

by these lines as long as the

maximum current rating is

observed.

Driving higher volt-

age devices (up to 25V)

requires the use of an exter-

nal supply. JP6 should be in

its default position 1-4 to

provide a ground reference

to the relay power source.

Therefore only 4 outputs

(SP1-4) are available.

When the 9850 is DC pow-

ered, SP5 can be used since

the ground reference is

provided through the power

input.

9850 P3

Set Points Port

Pin 1- 5V Out

Pin 2 - SP2

Pin 3 - SP3

Pin 4 - SP5

Pin 5 - SP1

Set Points

BRN (NC)

WHT

BLUE

BLK

GREY

7Vdc-25Vdc

Snubber Diodes

not required

Driving Externally Powered Coil Relays

Limit 150mA ea

max coil current

Pin 5 - SP4

PINK

Insulate Brn

Wire

Insulate all unused wires.

JP6 in Position (1-2)

9850 &

Relay

Power

Source

+

+

+

+

+

+

To 9850 DC Power

Input. Negative

Power shared.

Go to Index

Advertising
This manual is related to the following products: