BINDER UF V 500 User Manual

Page 58

Advertising
background image

UF V (E2+E2.1) 03/2013

page 58/112


Display Setting range

Operating function

0 to 999

Password request

Entry of the password that has been defined in operating mode HAND in

operating function “

PA.H” (chap. 8.2). The operating functions’ settings in

operating mode HAND are temporarily unlocked.

8.4.3 Permanently unlocking the operating functions of operating mode HAND

To permanently unlock the settings, set operating function “

PA.H” to “0” in HAND mode (chap. 8.2).


8.5 Performance during and after power failure and shut down

In the event of power failure, the battery maintains the controller functions. The controller display is dark

and can be activated for 5 seconds by pressing any button. The refrigerating machine is out of operation..

The unit’s refrigerating function can be maintained through the optional CO2 emergency cooling (chap.

11). The zero-voltage relay alarm output (8) (chap. 10.10) is switched for the whole duration of the power

failure.
After the power returns, each freezer turns on with an individual firmly assigned delay of max. 180 sec-

onds to prevent current spikes in the customer's electricity supply system by simultaneously switching on

several devices.
The controller counts down the time until restart in seconds.






Figure 37: Time until restart


After the power returns or when turned on by hand, the freezer regulates the temperature to the last en-

tered set point.

All settings and set point values remain in the memory during power failure after power off.