1 indications and alarm functions overview, 2 resetting the alarm messages – BINDER UF V 500 User Manual

Page 61

Advertising
background image

UF V (E2+E2.1) 03/2013

page 61/112

10. Indications and alarm functions (auto-diagnostic system)

10.1 Indications and alarm functions overview

When operational faults occur, the controller triggers visual and audible alarm signals. The red collective

alarm LED

flashes when an alarm signal is emitted, and an audible alarm (intermittent buzzer)

sounds.
A zero-voltage relay alarm output (8) (chap. 10.10) permits transmission of the alarm e.g., to a central

monitoring system.
The alarm messages safety controller or tolerance band + door open are displayed cyclically one after

the other if they occur simultaneously.
If more than one alarm signal is sent simultaneously, they are displayed in a cycle, except for alarms 997

to 999. These take priority over all other operational displays and alarm signals of the controller.
Except for the tolerance range alarms, all alarms are displayed immediately when the fault occurs. The

tolerance range alarms are suppressed for a selected time (delay times set for temperature alarm) after

opening the unit door or turning on the freezer.

Find an overview of all alarm indications on the controller in chap. 17.2.

WARNING: If customer should use a freezer running in non-supervised continuous opera-

tion, we strongly recommend in case of inclusion of irrecoverable specimen or samples to

split such specimen or samples and store them in at least two chambers, if this is feasible.

10.2 Resetting the alarm messages

Eliminate the cause of the alarm or wait until the unit compensates for the error.

The visual alarm (alarm message and indication by LED) disappears, when the cause of the fault has

been remedied or the alarm message has been reset with the “EXIT” key.

Press the “

EXIT” button to switch off the audible alarm signals.

Advertising
This manual is related to the following products: