Table 1 Temperature requirements

Item Temperature

Operating temperature

0°C to 45°C (32°F to 113°F)

Storage temperature

–40°C to 70°C (–40°F to 158°F)

Table 2 Humidity requirements

Item Relative

humidity

Operating humidity

5% to 95%

Storage humidity

5% to 95%

Altitude

Table 3 Altitude requirements

Item Altitude

Operating altitude

–60 m (–196.85 ft) to 4 km (2.49 miles)

Storage altitude

–60 m (–196.85 ft) to 4.5 km(2.8 miles)

Cleanness

Dust buildup on the chassis may result in electrostatic adsorption, which causes poor contact of metal

components and contact points, especially when indoor relative humidity is low. In the worst case,

electrostatic adsorption can cause communication failure.

Table 4 Dust concentration limit in the equipment room

Substance Concentration limit (particles/cu m)

Dust particles

≤ 3 x 10

4

(No visible dust on desk in three days)

NOTE:

Dust particle diameter ≥ 5 μm

The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and

premature aging of components, as shown in

Table 5

.

Table 5 Harmful gas limits in an equipment room

Gas Max.

(mg/m

3

)

SO

2

0.2

H

2

S 0.006

NH

3

0.05

Cl

2

0.01