Xantrex Technology XMP 2600 User Manual

Page 28

Advertising
background image

Installation

Rear

Panel

Description

option 2

Vin=0V

modules operation inhibited

Vin=4VDC to 12VDC

modules operation enabled

Connect as follows:

+Vin @

pin

3

-Vin @

pin

11

Short pins #5 and #13.

the +Vin and -Vin terminals are isolated and can be floated up to
±200VDC relative to the earth potential.

option 3

+/-SHORT shorted

modules operation enabled

+/-SHORT open

modules operation inhibited

Connect as follows:

+SHORT @

pin

2

-SHORT @

pin

11

Short pins #1 and #9.

Short pins #4 and #12.

the -SHORT pin is the GND of the RS-232 and the IEEE-488.

option 4

+/-SHORT shorted

modules operation inhibited

+/-SHORT open

modules operation enabled

Connect as follows:

+SHORT @

pin

2

-SHORT @

pin

11

Short pins #1 and #9.

Short pins #4 and #12.

Short pins #5 and #13.

the -SHORT pin is the GND of the RS-232 and the IEEE-488.

The dry contact outputs are as follow:

Pin #7 shorted to pin #6 when the modules are operating.

Pin #7 shorted to pin #14 when the modules are not operating.

These output indications are floating, isolated to 200VDC from earth ground.

XMP 2600 User’s Guide

rev. 1.0

9