Setting protection thresholds, Rotection parameter display, Protection parameter display – Xantrex Technology XMP 2600 User Manual

Page 69

Advertising
background image

Setting protection thresholds

Basic operation

However, some times you may wish to limit the output settings allowed values to
protect sensitive loads that will not tolerate the full output ratings.

For that end you use the limit parameter (Vlim and Ilim): the values you program for
the limit parameter are used as upper limits when you program output settings.

To set values for the limit parameter, proceed as follows:

Select the power module to program (see: first operation steps chapter
for details).
Select the LIM parameter (use the up / down selection keys) and enter
programming mode (press the SET key) or enter programming mode
and then select the LIM parameter (see: Programming power module
parameters at the beginning of this chapter).
Set voltage and current values for the limit parameter (see:
Programming power module parameters at the beginning of this
chapter).
Proceed to program other power module parameters or exit
programming mode by pressing the SET key.

Setting protection thresholds

To protect the connected load from excessive output voltage or current delivery by
the power module that feeds it, protection mechanisms are continuously monitoring
the module’s output voltage and current.

When the output’s voltage or current exceed a pre-defined level a fault event is
generated and the power module shuts down.

If the power module’s control circuit ascertains that the module cannot shut down its
output the XMP’s main controller is informed and the main converter is shut down.

Protection thresholds are set using the PROT parameter.

Protection

parameter

display

When viewing (in status mode) or programming the protection parameter, the
operating mode and foldback selection indicators that are usually shown on the
display’s upper row are replaced with an indicator of protection threshold setting
method, as illustrated below.

Parameter

value

setting

method

cursor

system

symbol

system status

or instructions

condensed

modules status

Entry
guidance

Display in programming mode showing PROT values

50

XMP 2600 User’s Guide

rev. 1.0

Advertising