Input mains voltage rating, Do not open the unit, Air inlets and air outlet – Xantrex Technology XMP 2600 User Manual

Page 7: Output voltages, Nonoperative modules

Advertising
background image

Input Mains

Voltage

Rating

The XMP 2600 operates at the following mains nominal voltages:

170Vac - 265Vac nominal (45 to 66Hz)

120Vac nominal, up to 1KW output power (45 to 66Hz)

Do not exceed this voltage range (nominal), as deterioration of performance or
damage to the unit is likely to occur. The following table shows the mains voltage
specification of the Power Supply (for more detailed information please refer to the
Operating Conditions section of chapter 1):

Nominal Mains

Nominal Current

230Vac Iin<15A

120Vac, Po<1KW

Iin<15A

Mains supply voltage fluctuations may not exceed +/-10% of the nominal voltage.

Power plug shall be fitted according to each national electrical code, and rated for a
current of at least 20A.

WARNING

The XMP 2600 must be operated at the proper mains voltage. Before operating
the unit make sure the mains voltage complies with the range described above.
Noncompliance with the input voltage may cause hazard and damage to the unit!

Do Not Open

The Unit

The user, except when replacing modules, should not open the unit.

WARNING

Make sure the power cord is disconnected from the mains before opening the
unit. High voltages inside the unit may cause electric shock.

Air Inlets And

Air Outlet

The Power Supply is a forced air-cooled unit. Cooling is essential for the unit's
proper operation.

The unit includes four air inlet openings located in the front panel, in both the left
and right sides near the front panel and in the top cover near the front panel. The air
outlet is in the rear panel (all over its surface).

Make sure there are no obstructions for the airflow, at least two centimeters (0.8”)
away from these openings.

Obstructing these ventilation openings may cause fire and irreversible damage to the
unit.

Output

Voltages

The Power Supply's outputs (at the unit's rear) may carry high voltages. Make sure
to handle them properly to avoid shock hazard.

Unused outputs must be closed with load connectors (these connectors must include
sense lines connections).

Nonoperative

Modules

Do not operate the unit if it contains damaged or defective modules. Hazard or
damage may occur.

Damaged or defective units should be repaired by authorized personnel only.

f

XMP 2600 User’s Guide

rev. 1.0

Advertising