INSTALLATION AND CONNECTION

This chapter describes the procedures for the electrical and

mechanical installation of the Soft-Starter SSW-07. The guidelines

and suggestions must be followed for the correct operation of the

Soft-Starter SSW-07.

The location of the Soft-Starters SSW-07 is an important factor to

assure the correct operation and high product reliability.

Avoid:

Direct exposure to sunlight, rain, high moisture and sea air ;

Exposure to explosive or corrosive gases and liquids;

Exposure to excessive vibration, dust or any metallic and/or oil

particles in the air.

Allowed Environmental Conditions:

Surrounding air Temperature: 0 ºC to 55 ºC (32 ºF to 131 ºF) -

nominal conditions.

Relative air moisture: 5 % to 90 %, with no-condensation.

Maximum altitude: 1,000 m (3,300 ft) above sea level - nominal

conditions.

From, 1,000 m to 4,000 m (3,300 ft to 13,200 ft) above sea level -

current reduction of 1 % for each 100 m (330 ft) above 1,000 m

(3,300 ft).

From 2000 m to 4000 m (6,600 ft to 13,200 ft) above sea level -

voltage reduction of 1.1 % for each 100m (330 ft) above 2,000 m

(6,600 ft).

Pollution degree: 2 (according to the UL508).

Normally, only non conductive pollution. Condensation must not

cause conduction in the particles in the air.

The external dimensions and mounting holes are shown in figure

3.1 and table 3.1 below.

C

A

B

D

P

H

L

A

L

P

C

D

B

H

Figure 3.1 - SSW-07 dimensions

3.1 MECHANICAL

INSTALLATION

3.1.1 Environmental

Conditions

Chapter

3

3.1.2 Soft-Starter

SSW-07

Dimensions