CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS

40

English

5.1.2 Current Limit

Starting

1) To start with a current limitation it is necessary to start with a load.

Initial test without load can be done with a voltage ramp;

2) Set the acceleration time with the necessary starting time, initially

with short times, 20 to 25 seconds. This time will be used as the

stall time in case the motor does not start;

3) Set the current limit according to the conditions that your electric

installation allows, as well as to the values that supply enough

torque to start the motor. It can initially be programmed with values

between 2x and 3x the nominal current of the motor (ln of the motor).

I(A)

Start

I Limitation

I Nominal

Maximum Time

Current Limitation

0

t(s)

Enable

Disable

Figure 5.4 - Current limit starting

NOTES!

If the current limit is not reached during the start, the motor will

start immediately;

Very low Current Limit values do not provide sufficient torque to

start the motor. Always keep the motor rotating once it is started.

For loads that need a higher initial starting torque, the Kick Start

function can be used;

If faults occur during the start, check all the connections from the

Soft-Starter to the supply network, motor connections, supply

network voltage levels, fuses and circuit breakers.

1) To start with pump control a load is necessary. No-load tests can

be done with voltage ramp;

2) The starting parameters setting depend mainly on the types of

hydraulic installations. Thus we recommend optimizing factory

settings, if possible.

3) Check if the motor rotation direction is an indicated on the pump

frame. If not, connect the phase sequence as indicated at P620;

Figure 5.5 - Direction of rotation of a hydraulic centrifugal pump

5.1.3 Starting with

Pump Control

(P202 = 2)