CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS

39

English

5.1.1 Voltage Ramp

Starting

Current

Torque

T/Tn

Tn

I/In

Figure 5.2 - Characteristic curves of torque and current in a

current limitation start

1) Set the value of the initial voltage to a low value;

2) When a load is applied to the motor, set the initial voltage to a

value that makes the motor rotate smoothly from the instant it is

started.

3) Set the acceleration time with the necessary start time, initially

with short times, 10 to 15 seconds, and afterwards try to find the

best starting condition for the used load.

100 %Un

Start

U(V)

Disable

Voltage Ramp

Enable

t(s)

0

Figure 5.3 - Voltage ramp starting

NOTES!

With long starting times, or when the motor is without a load,

vibration can occur during the start of the motor, therefore lower

the starting time;

If faults occur during the start, check all the connections from the

Soft-Starter to the supply network, motor connections, supply

network voltage levels, fuses and circuit breakers.