3 mounting specifications, Chapter 3 - installation and connection – Xylem SSW-07 Soft-Starter User Manual

Page 14

Advertising
background image

CHAPTER 3 - INSTALLATION AND CONNECTION

13

English

table 3.1 - Installation data with dimensions in mm (in)

To install the Soft-Starter SSW-07 leave at least the free spaces

surrounding the Soft-Starter as in figure 3.2 below. The dimensions

of these free spaces are described in table 3.2.

SSW-07 Model

A

mm

(in)

B

mm

(in)

C

mm

(in)

17 A

24 A

30 A

50

(2)

50

(2)

30

(1.2)

45 A

61 A

85 A

80

(3.2)

80

(3.2)

30

(1.2)

130 A

171 A

200 A

100

(4)

100

(4)

30

(1.2)

255 A

312 A

365 A

412 A

150

(6)

150

(6)

30

(1.2)

table 3.2 - Recommended free spaces

Install the Soft-Starter SSW-07 in the vertical position according to

the following recommendations:

1) Install on a reasonably flat surface;

2) Do not put heat sensitive components immediately above the

Soft-Starter SSW-07.

ATTENTION!

If a Soft-Starter SSW-07 is installed on top of another use the

minimum distance A + B and diverge from the top Soft-Starter the

hot air that comes from the one beneath it.

3.1.3 Mounting

Specifications

* IP20 with optional.

SSW-07

Model

Height

H

mm

(in)

Width

L

mm

(in)

Depth

P

mm

(in)

A

mm

(in)

B

mm

(in)

C

mm

(in)

D

mm

(in)

Mounting

Screw

Weight

kg

(lb)

Degree

of

Protection

17 A

24 A

30 A

162

(6.38)

95

(3.74)

157

(6.18)

85

(3.35)

120

(4.72)

5

(0.20)

4

(0.16)

M4

1.3

(2.9)

IP20

45 A

61 A

85 A

208

(8.19)

144

(5.67)

203

(7.99)

132

(5.2)

148

(5.83)

6

(0.24)

3.4

(0.13)

M4

3.3

(7.28)

IP20

130 A

171 A

200 A

276

(10.9)

223

(8.78)

220

(8.66)

208

(8.19)

210

(8.27)

7.5

(0.3)

5

(0.2)

M5

7.6

(16.8)

IP00 *

255 A

312 A

365 A

412 A

331

(13.0)

227

(8.94)

242

(9.53)

200

(7.87)

280

(11.0)

15

(0.59)

9

(0.35)

M8

11.5

(25.4)

IP00 *