CHAPTER 3 - INSTALLATION AND CONNECTION

22

English

3.2.7 Control

and Signal

Connections

EMI - Electronic Interference

The Soft-Starter SSW-07 is developed to be used in industrial

systems (Class A) according to Standard EN60947-4-2.

It’s necessary to have a distance of 0.25 m (10 in) between the

Soft- Starter SSW-07 control cables and motor cables.

Example: PLC wiring, temperature controllers, thermocouple cables, etc.

Grounding of the Motor frame

Always ground the motor frame. The Soft-Starter SSW-07 output

wiring to the motor must be installed separately from the input wiring

as well as from the control and signal wiring.

The control connections (digital inputs and relay outputs) are made

through the terminals (refer to figure 3.9).

Terminal

Description

Specifications

Torque Nm

(in lb)

A1

Electronics Supply

Voltage: 110 to 240 Vac (-15 % to +10 %)

(models from 17 A to 200 A)

110 to 130 Vac or 208 to 240 Vac

(-15 % to 10 %) (models from 255 A

to 412 A).

0.5 (4.5)

A2

Grounding

Only for the 255 to 412 A models

Terminal

Factory Default

Specifications

DI1

Starts/Stops Motor

3 isolated digital inputs

Voltage: 110 to 240 Vac (-15 % to +10 %)

Current: 2 mA Max.

DI2

Fault reset

DI3

Fault reset

13

Relay 1 output - Operation

Contact capacity:

Voltage: 250 Vac

Current: 1 A

14/23 Relay common point

24

Relay 2 output - Full voltage

table 3.9 - Description of the control connector pins

Figure 3.9 - Control terminals of the Soft-Starter SSW-07

NOTE!

It is recommended to use shielded cables for the Dix inputs when

using long cables (above 30 m) in noisy environments. The metallic

shield and A2 must be grounded.