1 power supply capacity, 2 recommended fuses – Xylem SSW-07 Soft-Starter User Manual

Page 20

Advertising
background image

CHAPTER 3 - INSTALLATION AND CONNECTION

19

English

3.2.4.1 Power Supply

Capacity

3.2.4.2 Recommended

Fuses

NOTE!

Use the wire sizes and fuses recommended in tables 3.5 and 3.7.

The connector tightening torque is indicated in table 3.4. Use only

copper wires 70 °C (158 °F).

The Soft-Starter SSW-07 is suitable to be used in a circuit capable

of supplying not more than X (according to table 3.6) symmetrical

rms amperes, Y maximum volts when protected by ultra-rapid fuses.

SSW-07 Model

Y = 220-575 V

X (kA)

17 A

5

24 A

5

30 A

5

45 A

5

61 A

5

85 A

10

130 A

10

171 A

10

200 A

10

255 A

25

312 A

25

365 A

25

412 A

25

table 3.6 - Maximum current capacity of the power supply

The SSW-07 can be installed on power supplies with a higher

fault level, if it is protected by ultra-rapid fuses with an adequate

interrupting current and an I

2

t according to item 3.2.4.2.

The fuses to be used on the input must be high speed semiconductor

fuses with l

2

t lower or equal to 75 % of the SCR value indicated in

table 3.7 (A

2

s). The fuse rated current should preferably be equal or

greater than the motor starting current to avoid cyclic overloads and

fuse opening in the forbidden region of the Time x Current curve.

These fuses will protect the SSW-07 in case of a short-circuit.

Normal fuses can also be used, instead of the high speed, which will protect

the installation from short-circuits, but the SSW-07 will not be protected.

For the electronic supply protection of the SSW-07 must be used

fuse type D, or circuit breaker type C as specified in table 3.7.

SSW-07

Model

I²t of

the

SCR

(A²s)

WEG Fuses with CE Certification

Fuses with UL Certification (A)

Control

Fuse

Fuse

Nominal

Current

(A)

Fuse Model

(Blade Contacts)

Part

Number

WEG

Fuse

Nominal

Current

(A)

Ferraz Shawmut/

Mersen

Flush End Contacts

Cooper

Bussmann

Bolted

Contacts

17 A

720

63

FNH1-63-K-A 10806688

50

6.6URD30TTF0050 170M2611

2 A

(D Type)

or

2 A

Circuit

Breakers

(C Type)

24 A

4000

80

FNH00-80-K-A 10705995

80

6.6URD30TTF0080 170M1366

30 A

4000

100

FNH00-100-K-A 10707110

80

6.6URD30TTF0080 170M1366

45 A

8000

125

FNH00-125-K-A 10707231

100

6.6URD30TTF0100 170M1367

61 A

10500

160

FNH00-160-K-A 10701724

125

6.6URD30TTF0125 170M1368

85 A

51200

250

FNH00-250-K-A 10711445

200

6.6URD30TTF0200 170M1370

130 A 97000

400

FNH1-400-K-A 10815073

315

6.6URD31TTF0315 170M1372

171 A 168000

500

FNH2-500-K-A 10824109

450

6.6URD32TTF0450 170M3170

200 A 245000

630

FNH2-630-K-A 10824110

500

6.6URD32TTF0500 170M3171

255 A 90000

500

FNH3-500-K-A 10833056

400

6.6URD32TTF0400 170M5158

312 A 238000

710

FNH3-710-K-A 10833591

500

6.6URD33TTF0500 170M3171

365 A 238000

710

FNH3-710-K-A 10833591

550

6.6URD33TTF0550 170M5161

412 A 320000 2 x 500 A FNH3-500-K-A 10833056

700

6.6URD33TTF0700 170M6161

table 3.7 - Recommended fuses

Advertising