CHAPTER 6 - SOLUTION AND TROUBLESHOOTING

51

English

6.3 PREVENTIVE

MAINTENANCE

WARNING!

Always disconnect the general power supply before touching any

electric component associated to the Soft-Starter SSW-07.

Do not apply any high voltage tests on

the Soft-Starter SSW-07!

If necessary, consult the manufacturer.

Do not use megometers to test thyristors.

Periodic inspections of Soft-Starters SSW-07 and installations

are necessary to avoid operating problems due to unfavorable

environmental conditions like high temperature, moisture, dust,

vibrations or due to the aging of the components.

When the SSW-07 Soft-Starter is stored for a long period of time, it

is recommended that it be energized for 1 hour, each year.

Component

Abnormality

Corrective Action

Terminals, Connectors

Loose screws

Tightening

(1)

Loose connectors

Fans / Ventilation Systems

Dirty fans

Cleaning

(1)

Abnormal noise

Substitute fan

Fan always off

Abnormal vibration

Dust in the air filters

Cleaning or substitution

(2)

Power Module / Power

Connections

Accumulated dust, oil, moisture, etc. Cleaning

(1)

Screws with loose connections

Tightening

(1)

table 6.3 - Periodic inspections after putting into use

(1) Every six months.

(2) Twice a month.