CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS

46

English

Example of readjustment of the nominal current:

I

SSW-07

= 30 A

I

MOTOR

= 25 A

S. F. = 1.15

Setting of the Motor Current = I

MOTOR

x S.F. / I

SSW-07

= 25 A x 1.15 /

30 A = 96 %

ATTENTION!

The increased motor current has direct impact on the maximum

thermal class, that protects the motor, even if the S.F. parameter is

set.

Determine the maximum thermal class, considering the service

factor:

Stall Current = 6.6 x ln

Hot Stall Time = 6 s

Service Factor = 1.15

Before the maximum thermal class is verified in figure 4.9, the stall

current must be divided by the service factor.

Stall Current / S.F. = 6.6 / 1.15 = 5.74

5.74 x In of the motor

t(s)

6 s

0

xln

25

Hot

20

15

Figure 5.12 - Checking of the maximum thermal class, considering the S.F.

Class 20 is the highest class that protects the motor, if the service

factor is used.