CHAPTER 4 - SETTING THE SSW-07

36

English

4.9 RESET

4.10 DI2 DIGITAL

INPUT SETTING

A fault condition can be reset using the RESET key at the front of

the SSW-07 or through a push-button (0.5 seconds) at DI3 (digital

input for RESET). Another way to reset the SSW-07 is by switching

Off/On the electronic power supply (A1 and A2).

NOTE!

The SSW-07 also allows for the possibility of automatic RESET by

enabling this function through the DIP Switch (auto):

Automatic RESET occurs after 15 minutes in the following

conditions:

-Overcurrent;

-Phase loss;

-Stall;

-Overcurrent before By-pass;

-Frequency out of range;

-Contact of the internal By-pass relay is open;

-Power control supply undervoltage;

-External fault.

For incorrect phase sequence there is no automatic RESET.

For electronic overload of the motor there is a specific algorithm

for the automatic RESET time.

In the factory default, the DI2 digital input has its function programmed

for the reset of faults. DI2 can also be programmed to work as a

three wire control.

The three wire control allows the Soft-Starter to be commanded

through two digital inputs, DI1 as an ON input and DI2 as an OFF

input. This allows for the direct placement of two push buttons.

Refer to item 3.3.2.

To change the DI2 digital input, follow the instructions below:

1. To enter in programming mode, maintain the reset key at the

front of the SSW-07 pressed for 5 seconds. Maintain the reset

key pressed during programming;

2. When in programming mode, two LEDs will turn on (overcurrent

and phase loss), indicating that DI2 is programmed for fault Reset.

When three LEDs turn on (overcurrent, phase loss and phase

sequence), it indicates that the DI2 is programmed for three wire

commands;

3. To change the programming to three wire commands, move the

overcurrent DIP Switch and return to the previous position. The

three LEDs will turn on, indicating that DI2 is programmed for

three wire commands;

4. To change the DI2 programming to fault Reset, move the Kick

Start DIP Switch and return to the previous position. Two LEDs

will turn on, indicating that the DI2 is programmed for fault Reset;

5. Programming is concluded when the reset key is released.