CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS

42

English

10)Set P610 and P611 to current and time levels that prevent the

hydraulic pump from running without a load.

Disable

Enable

0

100%Un

Stop

Start

Pump Control

P104

P102

P105

t(s)

P103

P101

U(V)

Figure 5.8 -

Start with pump control

NOTES!

1) If the hydraulic piping is not fitted with a manometer, the water

hammer can be noted at the pressure relief valves;

2) Please, consider that sudden line voltage drops results in motor

torque drops. Thus, ensure that the power supply line characteristics

are within the characteristics required for motor operation;

3) If errors are detected during the motor start, check all connections

of the Soft-Starter to the power line, the motor connections, the

voltage levels of the power line, the fuses, circuit-breakers and

disconnecting switches.

Is recommended program the control type in pump control using

keypad or serial communication, see the Programming Manual

for more details. In special cases, when is not available keypad or

serial communication, is also possible to program the control type

in pump control following these instructions:

1) To enter in programming mode, keep the reset key at the SSW-07

front cover pressed during 5 seconds, keeping it also pressed

throughout the programming;

2) When in the programming mode, LEDs will turn on indicating the

actual parameterization. See item 4.10 and 4.12;

3) To modify the control type, change the Stall DIP Switch and put

it back in the previous position. The Stall LED will indicate the

new programmed control type:

- LED Stall off: P219=0. Control type defined through Voltage

Ramp/Current Limit DIP Switch.

- LED Stall on: P219=2. Control type in Pump Control and

parameterization through Trimpots and DIP Switches.

5.1.4 Programming

the control type

in pump control