Chapter 3 - installation and connection – Xylem SSW-07 Soft-Starter User Manual
Page 18
CHAPTER 3 - INSTALLATION AND CONNECTION
17
English
Figure 3.5 - Power terminals
table 3.4 - Maximum torque for power connection
3.2.2 Location of the Grounding, Control and Power Connections
Figure 3.6 - Location of the grounding, control and power connections
Models 17 A to 85 A
Models 130 A to 412 A
Dimensions in mm (in).
SSW-07
Model
Enclosure
Size
Line / Motor
Grounding
Screw/
Terminal
Torque
Nm
(in lb)
Screw
Torque
Nm
(in lb)
17 A
24 A
30 A
Size 01
Terminal
3
(27)
M4
(5/32”)
4.5
(40)
45 A
61 A
85 A
Size 02
Terminal
5.5
(49)
M5
(3/16”)
6
(53)
130 A
171 A
200 A
Size 03
M8
(5/16”)
19
(168)
M6
(1/4”)
8.3
(73)
255 A
312 A
365 A
412 A
Size 04
M10
(3/8”)
37
(328)
Terminal
0.5
(4.5)
BORNE DE SAIDA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE SAIDA
POTENCIA
Output Power
Terminal
Input
Power Terminal
Output
Power Terminal
Input
Power Terminal
R/1L1
S/3L2
T/5L3
U/2T1
V/4T2
W/6T3
R/1L1 S/3L2 T/5L3
ATERRAMENTO
ATERRAMENTO
ATERRAMENTO
CONTROLE
CONTROLE
CONTROLE
CONTROLE
ATERRAMENTO
62.8
(2.48)
36.3
(1.43)
84,8
(3.34)
13.3
(0.52)
114
(4.48)
148
(5.81)
56.3
(2.22)
60.5
(2.38)
22.7
(0.89)
39.7
(1.56)
25.1
(0.99)
197
(7.75)
32.7
(1.29)
14.8
(0.59)
14.8
(0.59)
33.0
(1.30)
39.0
(1.54)
39.0
(1.54)
48.2
(1.90)
63.0
(2.48)
75.5
(2.97)
75.5
(2.97)
63.0
(2.48)
Grounding
Control
Control
Control
Control
Grounding
Grounding