CHAPTER 4 - SETTING THE SSW-07

30

English

4.4 CURRENT LIMIT

SETTING

NOTE!

The Initial Voltage trimpot has an initial voltage setting function only

when the kind of control is programmed to start with a voltage ramp.

This setting defines the maximum limit of the current during motor

starting in percentage of the nominal current of the Soft-Starter.

If the current limit is reached during the start of the motor, Soft-

Starter SSW-07 will maintain the current at this limit until the motor

reaches nominal speed.

If the current limit is not reached, the motor will start immediately.

The current limitation should be set to a level that the motor

acceleration can be observed, otherwise the motor will not start.

Current Limit

Setting Trimpot

Figure 4.4 - Current limit setting

NOTES!

If at the end of the acceleration ramp (set at the Trimpot Acceleration

Time), full voltage is not reached, a start timeout Fault will be shown.

This fault is indicated through the Fault LED flashing twice with the

Ready LED on.

The trimpot Current Limit has a Current Limit setting function only

when the kind of control is programmed to start with a Current Limit.