CHAPTER 4 - SETTING THE SSW-07

31

English

4.6 DECELERATION

RAMP TIME

SETTING

When Soft-Starter SSW-07 is programmed to Voltage Ramp control,

this is the voltage increment ramp time.

When Soft-Starter SSW-07 is programmed to Current Limit control,

this time is used as the maximum starting time, working as a

protection against blocked rotors.

Acceleration Ramp

Time Setting Trimpot

Figure 4.5 - Acceleration ramp time setting

NOTE!

The programmed acceleration time is not the exact motor

acceleration time, but the time of the voltage ramp or the maximum

starting time. The motor acceleration time depends on the motor

characteristics and the load.

Please consider that in cases where the relation of the SSW-07

current and the motor nominal current is 1.00, the maximum time

that the SSW-07 can work with 3 x In is 30 seconds.

Enables and sets the time of voltage decrease.

This setting should be used only for the deceleration of pumps to

reduce the water hammer. This setting must be made to achieve

the best pump performance.

NOTE!

This function is used to lengthen the normal deceleration time of a

load and not to force a lower time than that imposed by the load itself.

4.5 ACCELERATION

RAMP TIME

SETTING