CHAPTER 3 - INSTALLATION AND CONNECTION

25

English

3.3.3 Recommended

Set-up with

Command

via Two-wire

Digital Inputs

and Direction of

Rotation

Figure 3.12 - Recommended Set-up with Command via Two-wire Digital

Inputs and Direction of Rotation

NOTE!

To program the parameters shown above, is necessary the use of

keypad or serial communication. See the Programming Manual for

more information.

24

23

14

13

DI3

RL1

RL2

T1

P E

R
S
T

K1

K2

K2

K1

DI2

DI1

A2

A1

M

3~

R S T

U V W

P220 = 1

P230 = 1

P263 = 1 (DI1 = Start/Stop two

wires)

P265 = 4 (DI3 = Rotation

Direction)

P277 = 4 (RL1 = FWD/REV - K1)

P278 = 4 (RL2 = FWD/REV - K2)

Refer to notes in item 3.3.