CHAPTER 8 - TECHNICAL CHARACTERISTICS

English

8.4 ELECTRONICS AND PROGRAMMING DATA

8.3 POWER DATA

Power Supply Power Voltage (R/1L1, S/3L2, T/5L3) (220 to 575) Vac (-15 % to +10 %), or

(187 to 632) Vac

Frequency

(50 to 60) Hz (±10 %), or (45 to 66) Hz

Capacity

Maximum number of starts per hour

(without ventilation)

10 (1 every 6 minutes; models from 17 A to 30 A)

3 (1 every 20 minutes; models from 45 A to 200 A)

10 (1 every 6 minutes; models from 255 A to 412 A)

Maximum number of starts per hour

with optional ventilation Kit

10 (1 every 6 minutes; models from 45 A to 200 A)

Start cycle

3 x In of the SSW-07 during 30 seconds

Thyristors (SCRs)

Reverse voltage with 1600 V maximum peak

Overvoltage category

III (UL508/EN61010)

Power Supply

Control voltage

Connector (A1, A2)

(110 to 240) Vac (-15 % to +10 %), models from 17 A to 200 A

(110 to 130) Vac or (208 to 240) Vac (-15 % to +10 %) (models

from 255 A to 412 A)

Frequency

(50 to 60) Hz (±10 %), or (45 to 66) Hz

Consumption

15 VA models from 17 A to 200 A

60 VA continuos

800 VA additional during By-pass closing (models from 255 A

to 412 A).

Control

Method

Voltage ramp;

Current limitation.

Inputs

Digitals

3 Isolated digital inputs;

Minimum upper level: 93 Vac;

Maximum lower level: 10 Vac;

Maximum voltage: 264 Vac;

Input current: 1.1 mA @ 220 V;

Programmable functions.

Outputs

Relay

2 relays with NO contacts, 240 Vac, 1 A, and programmable

functions.

Safety

Protections

Overcurrent;

Phase loss;

Inverted phase sequence;

Heatsink overtemperature;

Motor overload;

External fault;

Open By-pass contact;

Closed By-pass contact;

Overcurrent before By-pass;

Stall;

Frequency out of range;

Electronic supply undervoltage.