1 standard three-wire connection, 6 grounding connections, Chapter 3 - installation and connection – Xylem SSW-07 Soft-Starter User Manual

Page 22

Advertising
background image

CHAPTER 3 - INSTALLATION AND CONNECTION

21

English

3.2.6 Grounding

Connections

Figure 3.8 - Grounding connections for more than one Soft-Starter SSW-07

Line current of the Soft-Starter SSW-07 is equal to the motor current.

1/U1

4/U2

2/V1

5/V2

6/W2

3/W1

2/V1

5/V2

1/U1

4/U2

6/W2

3/W1

R

S

T

N

PE

R

S

T

N

PE

T

W

V

S

U

R

T

W

V

S

U

R

Figure 3.7 - Soft-Starter SSW-07 with standard connection

DANGER!

The Soft-Starter must be grounded for safety purposes (PE).

The ground connection must comply with the local regulations.

Make the ground connection to a grounding bar or to the general

grounding point (resistance ≤10 ohms).

DANGER!

The AC input for the Soft-Starter SSW-07 must have a ground

connection.

DANGER!

Do not use the neutral conductor for grounding purpose. Use

dedicated ground conductor.

ATTENTION!

Do not share the ground wiring with other equipment that operate

with high current (for examples: high voltage motors, welding

machines, etc.). When several Soft-Starters SSW-07 are used,

observe the connections in the figure 3.8.

3.2.5.1 Standard

Three-Wire

Connection

BARRA DE ATERRAMENTO

INTERNA AO PAINEL

BARRA DE ATERRAMENTO

INTERNA AO PAINEL

GROUNDING BAR
INTERNAL TO THE PANEL

GROUNDING BAR
INTERNAL TO THE PANEL