CHAPTER 6 - SOLUTION AND TROUBLESHOOTING

49

English

Protection

Description and

Fault Display

Activation Description

Probable Causes

Reset

Undervoltage

in the control

supply

E70

(LED Fault)

Flashes twice

(LED Ready)

Off

Activates when the control

supply voltage is lower than 93

Vac.

Electronics supply lower than the

minimum value.

Electronics power supply with loose

contact.

Electronics power supply fuse blown.

Power-on.

Reset key.

Auto-reset.

DIx.

Internal

By-pass relay

contact Open

E71

(LED Fault)

Flashes 3 times

(LED Ready)

Off

When there is a fault with the

internal By-pass relay contacts

at full voltage.

Loose contact in the starting cables

of the Internal By-pass relays.

Defective By-pass relay contacts due

to an overload.

Incorrect electronic supply voltage,

only for SSW-07 models 255-412 A.

Power-on.

Reset key.

Auto-reset.

DIx.

Overcurrent

before the

By-pass

E72

(LED Fault)

Flashes 4 times

(LED Ready)

Off

Activates before the closing

of the By-pass if the current is

greater than:

37.5 A for the models up to 30 A;

200 A for the models from

45 to 85 A;

260 A for the model of 130 A;

400 A for the models from

171 and 200 A.

824 for the models from 255 A to

412 A.

The time programmed for the

acceleration ramp is shorter than the

actual acceleration time.

Nominal motor current higher than

the current that can be supported by

the Soft-Starter.

Motor shaft is locked, rotor blocked.

Power-on.

Reset key.

Auto-reset.

DIx.

Frequency out

of tolerance

E75

(LED Fault)

Flashes once

(LED Ready)

Off

When the limit is higher or lower

than the limits of 45 to 66 Hz.

The line frequency is out of range.

When the Soft-Starter + motor are

being supplied by a generator that

is not supporting the full load or the

start of the motor.

Power-on.

Reset key.

Auto-reset.

DIx.

Closed By-pass

contact or

shorted SCR’s

E77

(Fault LED)

flashes 6 times

(Ready LED) is

off

When the SSW-07 does not

detect voltage difference

between the input and output

at the moment the motor is

switched off.

Bad contact in the bypass cables.

By-Pass contacts are welded.

Short-circuited thyristor.

Input and output external short-

circuit.

Disconnected motor.

Power-on.

Reset key.

DIx.

table 6.1 - Faults and possible causes (cont.)