CHAPTER 3 - INSTALLATION AND CONNECTION

23

English

3.3 RECOMMENDED

SET-UPS

Some recommended set-ups are shown here and they can be

completely or partly used.

The main warning notes for all the recommended set-ups are

shown below and are described in the schemes by their respective

numbers.

NOTES!

The use of fuses or circuit breakers at the input circuit is

necessary for the entire installation protection. It is not necessary

to use ultra-fast fuses for the SSW-07 operation; however, their

use is recommended for the soft-starter complete protection.

The transformer “T1” is optional and must be used when there

is a difference between the line voltage and the electronic power

voltage.

In case that damage at the SSW-07 Soft-Starter power circuit

keeps the motor running (e.g., shorted thyristors), the motor

protection is obtained with the use of the power isolating

contactor (K1) or circuit breaker (Q1).

Start push-button.

Stop push-button.

Start/Stop switch. Bear in mind that when using two-wire digital

input command (normally open switch with retention), in case

of a power interruption, upon return of power, the motor will be

started immediately if the switch remains closed.

In case of maintenance of the Soft-Starter SSW-07 or the motor

it is necessary to remove the input fuses or disconnect the power

supply to ensure the complete equipment disconnection from

the power supply.

The emergency stop can be used by disconnecting the

electronics power supply.

Undervoltage release for the Q1 power isolation circuit breaker.