CHAPTER 3 - INSTALLATION AND CONNECTION

14

English

For Soft-Starters SSW-07 installed in panels or closed metallic

boxes exhaustion/cooling is required so the temperature does not

exceed the maximum allowed. Refer to dissipated nominal power

in table 3.3.

3.1.3.1 Mounting

Inside a Panel

table 3.3 - Dissipated power for ventilator panel dimensioning

Figure 3.2 - Free spaces for ventilation

ATTENTION!

Independent conduits or cable trays must be planned for physic

separation of signal, control and power cables. (Refer to item 3.2

Electrical Installation).

C

SAIDA

FLUXO DE AR

B

A

ENTRADA

FLUXO DE AR

Air Flow

Inlet

Air Flow

Outlet

A

B

C

SSW-07

Model

Dissipated Power

in the electronics

(W)

Average Power

dissipated

10 starts/h

3 x In @ 30 s

(W)

Total Average Power

dissipated

10 starts/h

3 x In @ 30 s

(W)

17 A

12

15.3

27.3

24 A

12

21.6

33.6

30 A

12

27

39

45 A

12

41

53

61 A

12

55

67

85 A

12

77

89

130 A

12

117

129

171 A

12

154

166

200 A

12

180

192

255 A

12

230

242

312 A

12

281

293

365 A

12

329

341

412 A

12

371

383