Xylem SSW-07 Soft-Starter User Manual

Page 42

Advertising
background image

CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS

41

English

4) Set the initial voltage - P101 – so the motor starts smoothly as

soon as it is enabled.

5) Set the acceleration time according to the application, and, that

the motor is able to start the load smoothly, but the required

acceleration is not exceeded. If acceleration times are set too

long, this may result in vibration or harmful motor overheating;

6) To check the correct starting process, always use a manometer

in the hydraulic installation. Pressure increase should not result

in sudden oscillations. Thus the pressure increase should be as

linear as possible;

Enable

0

100%Un

Start

Pump Control

P102

P101

U(V)

Figure 5.6 - Manometer showing pressure increase

7) Program the deceleration initial voltage (P103) only when no

pressure drop is detected at the deceleration begin. With this

deceleration initial voltage you can improve the linear pressure

drop during the deceleration;

8) Set the deceleration time according to the application, and,

ensuring that the pump stops smoothly within the expected

limits. The set of excessively long times may result in vibrations

or harmful motor overheating;

Pára

0

100%Un

Parada

P104

P105

t(s)

P103

U(V)

Figure 5.7 -

Manometer showing the pressure drop

9) Generally, the current increases at the end of the deceleration ramp

and in this case the motor requires more torque to achieve a smooth

water flow stop. When the motor has already stopped, but is still

enabled, the current will increase too much. To prevent this condition,

set P105 to a value that as soon it stop it is also disabled;