CHAPTER 3 - INSTALLATION AND CONNECTION

20

English

3.2.5 Soft-Starter

SSW-07

Connection to

the Motor

NOTE!

The maximum I

2

t of the SSW-07 255 A fuse is smaller than 200 A

because of the thyristor constructive type used on this soft-starter.

When the SSW-07 is used in applications that require an isolator

contactor, according to the figure 3.10 (K1), the use of WEG

contactors is recommended.

SSW-07 Model

WEG Contactor

17 A

CWM18

24 A

CWM25

30 A

CWM32

45 A

CWM50

61 A

CWM65

85 A

CWM95

130 A

CWM150

171 A

CWM180

200 A

CWM250

255 A

CWM250

312 A

CWM300

365 A

CWME400

412 A

CWME400

table 3.8 - Recommended contactors

DANGER!

Power factor correction capacitors must never be installed at the

output of the Soft-Starter SSW-07. (U / 2T1, V / 4T2 and W / 6T3).

ATTENTION!

To ensure that the protections based on the current reading and

display operate correctly, for example the overload, the motor

nominal current must not be lower than 50 % of the nominal Soft-

Starter SSW-07 current.

NOTE!

Use the wire sizes and fuses recommended in tables 3.5, 3.6 and

3.7. The connector tightening torque is indicated in table 3.4. Use

only copper wires.

NOTE!

The Soft-Starter SSW-07 is provided with electronic protection

against motor overload. This protection must be set according to

the specific motor. When several motors are connected to the same

Soft-Starter SSW-07 use individual overload relays for each motor.

3.2.4.3 Recommended

Contactors