Chapter 1 Specifications Check

22

IA Net

XSEL-R/S

1.2 Basic Specifications List

Item

Description

Remarks

Communication System Half-duplex multi-drop

Insulation with pulse transformers

Baud Rate

12Mbps

ņ

Number of Connectable

Units

64 units at maximum

There are restrictions in the number of

units depending on the system

construction of the network.

[Refer to Chapter 3 Operation]

Occupied Memory Units 1 to 4 stations

XSEL : 1 to 4 stations to be occupied

Expansion I/O Unit : 4 stations to be

occupied

Shared Memory

Capacity

256 words

1 station (4 words) × 64 areas

Cycle Time

(Note 1)

0.102msec

(when 2 units connected) to䎃

2.365msec

(when 64 units connected)

Refer to 3.1.3 Regarding Communication

Cycle Time

Cable

Dedicated Cable

(CB-RS-IAN * * *)

Shielded two-cored twisted pair cable

Total Cable Length

100m

ņ

Terminal Resistance

External mount

100: (1/2W) necessary on both terminals

XSEL Side MCDN1.5/3-G1-3.5P26THR

Manufactured by PHOENIX CONTACT

Connector

Cable Side FMC1.5/3-ST-3.5

Manufactured by PHOENIX CONTACT

Note1 The calculation for IA Net communication cycle time is based on the last station number.

When 2 units connected(= final station No.1)

{(1+152) Ч (1 + 3) Ч 2} / 12000 = 0.102ms

When 64 units connected(= final station No.63)

{(63 + 152) Ч (63 + 3) Ч 2} / 12000 = 2.365ms