Chapter 3 Operation (Construction for Network)

43

IA Net

XSEL-R/S

Note Establishing the resizing station number and final station number parameters will speed up

networked communication, as unused stations are skipped in the communications polling.

[Setting 2: Setting of Resizing Station Number and Final Station Number]



Set the resizing station number (settable range from 0 to 63) to I/O Parameter No.603.

(Set the top station number of the first XSEL controller unit.)

Set the final station number (settable range from 1 to 63) to I/O Parameter No. 604.

(Set the top station number of the last networked device.)

Shown below is an example for setting (when connecting four units of XSEL).

Shared Memory Area

Station No.

0

1

2

3

4

5

6

7

8

9

10

11

··

61

62

63

64

··

[Caution in Setting]

1 For I/O Parameters No.603 and 604, set the same values in common for all the XSEL

controllers. If not the same value, “548: IA Net Resizing Overlapping Error” will be

generated.

2 When a change is made to a value in I/O Parameters No. 603 or 604, it is necessary

to either cold reboot (power cycle) all networked IA Net devices (all networked

controllers) or perform a simultaneous software reset on all controllers.



XSEL 1st Unit

(4 stations occupied)

XSEL 2nd Unit

(2 stations occupied)

XSEL 3rd Unit

(3 stations occupied)

XSEL 4th Unit

(1 station occupied)

No.603=0

No.604=11

No.603=0

No.604=11

No.603=0

No.604=11

No.603=0

No.604=11

Not used

Not used