Ia net, Xsel-r/s, Chapter 3 operation (construction for network) – IAI America XSEL-S User Manual

Page 45

Advertising
background image

Chapter 3 Operation (Construction for Network)

39

IA Net

XSEL-R/S

[2] Example for Parameter Setting and Shared Memory Assignment

The following tables show the parameter settings for the three networked XSEL controllers, when

connected and configured as shown in the completed construction map above.

Noto Add color code for Shared Memory Map here: see next markup page.

Shared Memory

Extension Input

32 Points

Extension Output

0 Points

Inputs: 80

(32 points of

extension I/O unit

inputs excluded)

Outputs: 208

(0 points of extension

I/O unit outputs

excluded)

Extension Input

0 Points

Extension Output

16 Points

Extension Input

64 Points

Extension I/O Unit 3 Unit Number

1

2

3

4

Extension Output

32 Points

XSEL

1st Unit

XSEL

2nd Unit

XSEL

3rd Unit

Inputs: 208

(0 points of

extension I/O unit

inputs excluded)

Outputs: 80

(16 points of

extension I/O unit

outputs excluded)

Inputs: 176

(64 points of

extension I/O unit

inputs excluded)

Outputs: 32

(32 points of

extension I/O unit

outputs excluded)