Ia net, Xsel-r/s, Chapter 4 appendix – IAI America XSEL-S User Manual
Page 76: Xcold start level

Chapter 4
Appendix
70
IA Net
XSEL-R/S
x
Cold Start Level
No.
Error Name
Contents / Counteractions
548
IA Net Resizing Overlapping Error
Several stations executed the resizing. There is a concern multiple
stations are subject to resizing execution. Check the conformity of I/O
Parameter No.603 with the controller on the same network.
54C
IA Net Communication Parameter
Error
There is a failure in the communication parameters of IA Net. Check in
I/O Parameters No.601 to 606 and other considerable numbers.
552
IA Net Link Error
IA Net Link Error was detected. Confirm that all the controllers
occupying the stations indicated in I/O Parameters No.603 and 604
are connected properly to IA Net.
This error also occurs when the occupied stations indicated in I/O
Parameters No.601 and 602 are duplicating with other controllers
connected to IA Net.
553
IA Net Message Command Sending
Busy Error
Message command could not be sent due to the busy condition at the
process of IA Net message command sending.
554
IA Net Message Command Sending
Timeout Error
IA Net message command could not be completed to be sent in the
specified time. There is a concern of message commands not being
able to be sent properly.
556
IA Net Message Command Area
Access Right Acquirement Timeout
Error
Access right to IA Net message command area could not be gained in
the specified time.
560
Number of IA Net Occupied Station
Exceeded Error
The number of IA Net occupied stations has exceeded the number
allowed in the system.
561
IA Net I/O Assignment Number
Overflow Error
The number of IA Net I/O assignments has exceeded the specified
range.
562
Extension I/O Unit Parameter Error
There is a failure in the extension I/O unit parameters.
It could be considered that;
1) The station numbers for a controller and an extension I/O unit are
duplicated,
2) An extension I/O unit with a station number greater than the value
set in I/O Parameter No.604 “IA Net Final Station No.” is attempted
to be used, or
3) Extension I/O unit is subject to the resizing executed station.
563
Extension I/O Unit DO Duplication
Error
Multiple controllers attempted to use DO in one I/O board on the
extension I/O unit.
564
Extension I/O Unit Initial
Communication Timeout Error
Initial communication with the extension remote I/O unit was not
established correctly.
It could be considered that;
1) Extension remote I/O unit is not connected,
2) Power is not supplied to extension remote I/O unit,or
3) Wrong unit number is set in I/O parameters.
565
Extension I/O Unit Board Undetected
Error
I/O board in an extension I/O unit was not detected.
566
Extension I/O Unit Undefined Error
Code Detection
Undefined extension I/O unit error code was detected.
This error occurs when the main CPU board software is not applicable
for the error code of the extension I/O unit. Updating is required on the
application in the main CPU board.
567
IA Net Communication Cycle Time
Error
There is an error in the communication cycle time of IA Net.
568
Extension I/O Unit Self Checking
Error
There is a failure in the CPU program of extension I/O unit.
569
Extension I/O Unit Initial
Communication Parameter Failure
There is a failure in the parameter acquired in the initial
communication with a controller.
678
Extension I/O Port Assignment
Parameter Error
There is an error in a parameter related to the extension I/O port
assignment.
679
Extension I/O Port Assignment
Number Overflow Error
The number of extension I/O port assignment exceeded the
specification range.
67A
Extension I/O Port Duplicated
Assignment Error
Extension I/O port assignment has duplicated.
For the set values in Parameter No. 701, make sure not to include the
number of output ports on an extension I/O unit.
D69
External Terminal Block Overcurrent
or Power Supply Failure
Overcurrent on external terminal block or an error in the power supply
to external terminal block.
E69
24V I/O Power Supply Failure
There is a failure in 24V I/O power supply.
E6C
DO Output Current Error
There is a failure in DO output current.