IAI America ACON-CY User Manual

Page 111

Advertising
background image

99

7. T

roubleshooting

Code Error

Cause/action

0CB Current-sensor

offset

adjustment error

The status of the current detection sensor in the controller is checked during
the initialization process. This alarm indicates that the sensor was found
abnormal as a result of this check.
Cause: [1] Faulty current detection sensor or peripheral component

[2] Inappropriate offset adjustment

Action: The board must be replaced or offset must be adjusted. Contact IAI.

0E0 Overload

Cause:

[1] The

load

increased

due to application of external force.

[2] If the actuator is equipped with a brake, the brake cannot be

released.

[3] The slide resistance of the actuator is large in some areas.

Action: [1] Check the load and its surroundings. If the load is receiving any

abnormal external force, make the necessary corrections to
remove the force.

[2] Turn on the brake release switch to see if the brake is released.

If the brake is not released, the brake itself may be faulty, or an
open cable or faulty brake circuit component in the controller is
suspected, among others.

[3] If the load can be moved by hand, do so to check for any area

where the slide resistance increases.

If [2] or [3] is the case, contact IAI.

Note:

Be sure to remove the cause of the alarm before resuming the
operation. If the power has been cut off, wait for at least 30 minutes
before reconnecting the power to prevent the motor coil from being
burned.

0E8 Open

phase

A/B

detected

Encoder signals cannot be detected correctly.
Cause: [1] The connector of the encoder relay cable is loose or its circuit is

open.

[2] The connector of the supplied actuator cable is loose or its

circuit is open.

Action: Check the connection condition of the encoder relay cable and

perform continuity check. If no abnormality is found, contact IAI.

0F4

Inconsistent PCB

This controller uses a different motor drive circuit depending on the motor
capacity, and therefore the installed printed circuit board (PCB) is also
different with each controller.
During the initialization after starting, the controller checks if the motor type
set by the manufacturer’s parameter matches the actual PCB installed.
This alarm indicates that the two do not match.
Cause: The parameter may not be entered correctly or the PCB may not be

assembled correctly.

Action: If you have encountered this error, contact IAI.

0F5 Nonvolatile

memory

verification error after
write

When data has been written to the nonvolatile memory, the written data is
read and compared (verified) against the written data for confirmation.
This alarm indicates that the read data does not match the written data.
Cause: [1] Faulty

nonvolatile

memory

[2] The memory has been rewritten more than 100,000 times. (The

nominal life of the nonvolatile memory is 100,000 rewrite
operations.)

Action: If the problem still persists after the power has been reconnected,

contact IAI.