Installation and wiring – IAI America ACON-CY User Manual

Page 33

Advertising
background image

21

3. Installation and W

iring

3.

Installation and Wiring

3.1

Installation Environment

3.2

Supplied Voltage

The controller takes a supplied voltage of 24 VDC ±10%.
For the load current of the actuator, refer to 2.1, “Basic Specifications.”

Pay due attention to the installation environment of the controller.

(1) When installing and wiring the controller, do not block the cooling ventilation holes. (Insufficient

ventilation will not only prevent the controller from demonstrating its full performance, but it may also
cause breakdown.)

(2) Prevent foreign matter from entering the controller through the ventilation holes. Since the enclosure

of the controller is not dustproof or waterproof (oilproof), avoid using the controller in a place subject
to significant dust, oil mist or splashes of cutting fluid.

(3) Do not expose the controller to direct sunlight or radiating heat from a large heat source such as a

heat treatment furnace.

(4) Use the controller in an environment free from corrosive or inflammable gases, under a temperature

of 0 to 40°C and humidity of 85% or less (non-condensing).

(5) Use the controller in an environment where it will not receive any external vibration or shock.
(6) Prevent electrical noise from entering the controller or its cables.
(7) The product can be used in an environment with Pollution Degree 2.