IAI America ACON-CY User Manual

Page 47

Advertising
background image

35

4. Position T

able Settings

(7) Positioning

band

x What this field means is different in “positioning operation” and “push-motion operation.”

“Positioning operation”:
In the proximity switch type, this field defines the width within which the movement
complete signal turns ON.
In the standard type, this field defines how far before the target position the movement
complete signal turns ON.
The factory setting is “0.1” mm.

In case of solenoid valve mode 0

Movement complete signal

Target position

Positioning band

In case of solenoid valve mode 1

Increasing the positioning band
quickens the starting of next sequence
operation, and consequently the tact
time becomes shorter. Set an optimal
value by considering the balance of the
entire system.

The movement complete
signal turns ON here.

Target position

Positioning band

“Push-motion operation”:

This field defines the maximum push distance to be applied
during push-motion operation from the target position.
Consider the mechanical variation of the work and set an
appropriate positioning band so that positioning will not complete
before the work is contacted.

The work is contacted and push-motion
operation is deemed complete, so the
movement complete signal turns ON here.

Work

Target position

Positioning band (maximum push distance)