IAI America ACON-CY User Manual

Page 74

Advertising
background image

62

5. Operation Using I/O Signals

5.3.4 Homing

This controller adopts an incremental position detector (encoder), so once the power is cut off, the mechanical
coordinates will be lost.
Accordingly, homing must be performed to establish the initial mechanical coordinate every time the power is
turned on.
To perform homing, input a rear end move command (ST0).

Operation timings

PLC processing 1: The rear end move command signal (ST0) turns ON when the start button is pressed.
Operation:

[1] The actuator starts moving toward the mechanical end on the home side.
[2] After contacting the mechanical end, the actuator reverses its direction and

temporarily stops at the home position.
o The homing complete signal (HEND) turns ON.

[3] The actuator moves toward the rear end, and stops at the rear end.

o The rear end positioning complete output (PE0) turns ON.

PLC processing 2: The rear end move command signal (ST0) turns OFF.
PLC processing 3: The actuator starts continuous operation.

Caution:

Take note of the following points regarding homing:
[1] Confirm that no obstacle exists between the actuator and the rear end.
[2] If an obstacle exists between the actuator and the rear end, move the actuator toward the

front end and remove the obstacle. The controller accepts a front end move command prior
to homing to accommodate the aforementioned condition.
In this case, the actuator moves forward at the homing speed and once the mechanical end
is reached, the front end positioning complete output (PE1) will turn ON.
This PE1 signal should be recognized as a tentative signal.

[3] Do not input an intermediate move command. (Even if an intermediate move command is

input, it will be ignored.)

Rear end move

command input (ST0)

Homing complete

output (HEND)

Rear end positioning

complete output (PE0)

Power-

on pos

ition

Mechanical end

Home position

Rear end

Max. 6 msec

[1]

[2]

[3]

Advertising