5. Operation Using I/O Signals

5.2.2

Timings after Power On

z Steps from Initial Startup to Actuator Adjustment

[1] Cancel the emergency stop or connect the motor drive power.
[2] Supply the 24-VDC I/O power (PIO connector pins 1 and 2).
[3] Supply the 24-VDC controller power (24-V and 0-V terminals on the power-supply terminal block).
[4] Set the minimum required parameters.

(Example)

x To temporarily disable the servo-on input because the PLC is not yet ready to accept the

input, change the value of Parameter No. 21 (Servo-on input disable selection) to “1.”

x To change the feed speed during teaching, change the value of Parameter No. 35 (Safety

speed).

[5] Input a servo-on signal from the PLC (if the servo-on input is enabled).
[6] Connect a PC or teaching pendant to adjust the actuator.

x Set optimal values in the “Position,” “Speed,” “Acceleration,” “Deceleration” and other fields

under Nos. 0 to 2 in the position table.

* If you have changed the value of Parameter No. 21 (Servo-on input disable selection) to “1,” the servo-on

input signal is not required.

Caution:

In the “Emergency stop actuated

o Turn on the power o Servo-on input o Cancel the

emergency stop” sequence, the servo will turn on up to 1.6 seconds after the emergency stop is
cancelled.

Safety circuit status

Supply of 24-VDC I/O
power

Supply of 24-VDC
controller power

* Servo-on input
(SON)

SV lamp (front panel)

Ready output (SV)

Emergency stop cancelled

Initial parameter

settings

An orange light comes
on for 2 seconds, and
then turns off.

Green

Max. 1.6 sec

Use a teaching pendant or PC to set
optimal values in the respective fields
under Nos. 0 to 2 in the position table.

Servo-on input

Max. 1.6 sec max

Emergency stop cancelled

Servo on