58

5. Operation Using I/O Signals

z Normal Operating Procedure

The operating procedure in a normal condition is explained below.
[1] Cancel the emergency stop or connect the motor drive power.
[2] Supply the 24-VDC I/O power.
[3] Supply the 24-VDC controller power.
[4] Input a servo-on signal from the PLC.
[5] First, input a rear end move command signal from the PLC (to cause the actuator to stand by at the rear

end).

[6] Start automatic operation.

Safety circuit status

Supply of 24-VDC
I/O power

Supply of 24-VDC
controller power

Servo-on input
(SON)

SV lamp
(front panel)

Emergency stop cancelled

Green

Max. 1.6 sec

Rear end move

command input (ST0)

Homing complete

output (HEND)

Rear end positioning

complete output (PE0)

Power

-on posi

tion

Mechanical end

Home position

Rear end

Start of continuous
operation

Max. 6 msec

When the SON signal has been input for the first time after turning on
the power, provide a delay of at least 1.6 seconds before inputting a
move command.
With each subsequent SON input, provide a delay of at least 60 msec.
(If the delay time is too short, the move command will be ignored.)