roubleshooting

7.4

Messages Displayed during Teaching Pendant Operation

This section explains the warning messages that may be displayed while operating the teaching pendant.

Code Message

Description

112

Input data error

An inappropriate value was input as a user parameter setting.
(Example) “9601” was input as the serial communication speed by

mistake.
Input an appropriate value again.

113
114

Input value too small
Input value too large

The input value is under the setting range.
The input value is over the setting range.
Input an appropriate value again by referring to the actuator specifications
and parameter list.

115

Homing not yet complete

The current position was written before homing was complete.
Perform homing first.

117

No movement data

No target position is set under the selected position number.
Input a target position first.

11E

Inconsistent data pair

The magnitude relationship of a pair of data is inappropriate.
(Example) The same value is set in both the + and – soft limit parameters.
Input appropriate values again.

11F

Absolute value too small

The minimum travel toward a target position is determined by the lead of
the drive system and encoder resolution.
This message indicates that the input target position is less than this
minimum travel.
(Example) If the lead is 20 mm, the encoder resolution is 800 pulses and

therefore the minimum travel is calculated as 0.025 mm/pulse
(20

y 800).

If 0.02 mm is input as the target position, this message will be
displayed.

121

Push search end over

The final position in push-motion operation exceeds a soft limit.
No harm is done as long as the actuator contacts the load. If it misses the
load, however, the actuator will reach the soft limit and this message will
be displayed.
Change either the target position or positioning band.

122

Multiple axes connected at
assignment

An axis number was assigned when multiple axes were connected.
Always assign an axis number when only one axis is connected.

180
181
182
183

Axis number change OK
Controller initialization OK
Home change all clear
I/O function changed

This is an operation check message.
(It does not indicate misoperation or error.)

202

Emergency stop

An emergency stop is currently actuated.

20A

Servo OFF during
movement

The servo ON signal (SON) was turned OFF by the PLC while the actuator
was moving. As a result, the servo turned OFF and the actuator stopped.