<10. EXPLOSION-PROTECTED TYPE INSTRUMENTS>

10-10

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

10.6 Intrinsically safe IECEx- components for category

3G (/ES3)

10.6.1 Technical data

Data of electronic transmitter type -E, -H and -J :
The electronic transmitter is an intrinsically safe device. This device is use for hazardous areas of category 3.

Applicable standards:

IEC 60079-0: 2007 edition 5

IEC 60079-11: 2006 edition 5

Type of protection

: Intrinsically safe Ex ic IIC T6 Gc

Ambient temperature

: -40°C ... +70°C

Safety relevant maximum values:
Maximum voltage

: U

i

= 30 V

Maximum current (IIC)

: I

i

= 101 mA

Maximum power

: P

i

= 1.4 W

Inner inductance

: L

i

= 0.15 mH

Inner capacity

: C

i

= 4.16nF

Data of limit switches :
The following table shows the maximum safety parameters for intrinsic safe limit switches according the certificates
IECEx PTB 11.0091X (Standard) and IECEx PTB 11.0092X (Fail Safe).
Table 10.4

Standard /K1 ... /K3

Ex ic IIC T6 TX

Fail Safe /K6 .../K10

Ex ic IIC T6 TX

Type 2

Type 3

Type 2

Type 3

Ui [V]

16

16

16

16

Ii [mA]

25

52

25

52

Pi [mW]

64

169

64

169

Ci [nF]

150

150

30

30

Li [µH]

150

150

100

100

max. ambient temp. [°C] for T6

49

28

49

28

max. ambient temp. [°C] for T5

61

40

61

40

max. ambient temp. [°C] for T4 - T1

89

68

89

68

Intrinsic safe power supply for the electronic transmitter :
The power supply for the electronic transmitter is an associated apparatus that may not be installed in the hazard-
ous area, and it may not exceed the safety relevant maximum values for voltage, current and power of the elec-
tronic transmitter as specified above.
For example option /UT can be used.

Intrinsic safe power supply for the limit switches :
The power supply (transmitter relay) for the limit switches is an associated apparatus that may not be installed in
the hazardous area, and it may not exceed the safety relevant maximum values for voltage, current and power of
the connected limit switch as specified above.
For example the type KFA6-SR2-Ex... (option (W2_) according certificate IECEx PTB 11.0031 (230V AC supply)
or the type KFD2-SR2-Ex... (option (W4_) according certificate IECEx PTB 11.0032 (24V DC supply) can be used.