<A2. SAFETY INSTRUMENTED SYSTEMS INSTALLATION>

A2-6

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

Table A2.24: Summary for RAMC ([V2]) with 4-20mA output – Failure rates

 

Profile 2

Profile 4

Fail Safe Detected (λSD)

0 FIT

0 FIT

Fail Safe Undetected (λSU)

60 FIT

60 FIT

Fail Dangerous Detected (λDD)

260 FIT

344 FIT

Fail Dangerous Undetected (λDU)

193 FIT

200 FIT

SFF

4

62.3%

66.8%

DC

D

57%

63%

MTBF

191 years

166 years

SIL AC

5

SIL1

SIL1

Safety metrics according to ISO 13849-1

6

:

MTTF

d

(years)

252

210

DC

57%

63%

Category (CAT)

CAT 1

CAT 2

Performance Level (required)

PL

r

= c

PL

r

= c

Performance Level (calculated)

4.53E-07 1/h

5.44E-07 1/h

T[Proof] = 1 year

T[Proof] = 5 years

T[Proof] = 10 years

PFDAVG = 9.28E-04

PFDAVG = 4.28E-03

PFDAVG = 8.46E-03

3

The switching contact output is connected to a fail-safe NAMUR amplifier (e.g. Pepperl+Fuchs KF**-SH-Ex1). The failure rates of the

amplifier are not included in the listed failure rates

4

The complete sensor subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for

reference only.

5

SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the

corresponding SIL but does not imply all related IEC 61508 requirements are fulfilled.

6

Depending on the application and possible external diagnostics a higher DCD and therefore also a higher category might be possible

to achieve.

7

The switching contact output is connected to a standard switching amplifier (e.g. Pepperl+Fuchs KF**-SR2-Ex*.W). The failure rates of

the amplifier are not included in the listed failure rates.