<10. EXPLOSION-PROTECTED TYPE INSTRUMENTS>

10-14

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

Electronic transmitter non incendive

1 1

8160191

FM CONTROL DRAWING

WT-MAG

Amann

07.11.2000

Slotwinski

07.11.2000

CKECKED

DRAWED

UPDATE No.

Rev.

aa

DATE

EDITOR CHECKED

TITEL:

NAME

DATE

DWG. No.:

79664 WEHR

YOKOGAWA

GERMANY

b

09.06.06 Rü HL

Nonincendive

Hazardous (Classified) Location

Class I, Division 2, Groups A, B, C, D, T6

Nonhazardous Location

V

max

= 30V

I

max

= 100mA

P

max

= 1.4W

C

i

≤ 40nF

L

i

≤ 150µH

T

amax

= 70°C

Voc

= 30V

Isc

= 100mA

Po

= 1.4W

C

a

≥ 40nF + C

cable

L

a

≥ 150µH + L

cable

WT-MAG

Associated Nonincendive

field wiring apparatus

+
-
A

The nonincendive field wiring circuit concept allows interconnections of nonincendive

field wiring apparatus with associated nonincendive field wiring apparatus, using any of

the wiring methods permitted for unclassified locations.

Vmax ≥ Voc or Vt

Ca ≥ Ci + Ccable

La ≥ Li + Lcable

For this current controlled circuit the parameter Imax is not required and need not

be aligned with parameter Isc or It of the barrier or associated field wiring apparatus.

For guidance on installation see ANSI/ISA RP 12.06.01 "Installation of Intrinsically Safe

Instruments Systems for Hazardous (Classified) Locations".

Install in accordance with the National Electrical Code NFPA 70 for US jurisdictions.

Install in accordance with the Canadian Electrical Code C22.1-02 for Canada jurisdictions.

WARNING : Substitution of components may impair intrinsic safety. For installation,

maintenance, or operation instructions see instruction manual.