<7. HART-COMMUNICATION>

7-2

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

7.2 Connection

The connection is carried out in accordance with below figure. Please note, that the load resistor must have a
value between 250 and 500Ω .
The minimum power supply is 13.5V + (RL*20mA) ; RL = load resistor
The maximum power supply is 30V.
As connection cable a protected twisted cable pair is recommended.

15

4

6

3

1

14

12

10

11

8 7

9

U

F

G

RAMC

A

Power supply

U

Mains 230V AC

KFA6-SR2-Ex2.W

Option: /W2B

Transmitter Relay

Limit MI

N

Limit MAX

Option / KnE

Rotameter

4-20mA

Max

Min

12

11

10

9

Limit switches

EN 60947-5-6 (Namur)

One channel connection like

limit MAX

4-20mA

RL

HART-Communication

with HART-Communicatio

n

without HART-Communication

Power supply U/V

RL/Ohm

13,5V+(RL*20mA) ...

30V

13,5V ...30V

< (U-13,5V) / 20mA

250 ... 500 Ohm

-

+

-

+

-

+

-

+

~

~

+ -

+ -

F71.EPS