<6. ELECTRONIC TRANSMITTER (-E)>

6-11

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

6.2.7.4 Calculation of pulse rate

Concerning the final flow-value (Qmax ), which was declared in the customers order, the pulse rate is
calculated in factory and is written onto the sheet ´Data of Pulse Output (Option /CP)´, which is included. This
value can be transferred to a blank label of the also included sheet with unit-stickers and then fixed on the
scale. After changing the flow rate unit with F12 the pulse rate must be recalculated.
Calculation of pulse rate :
· Read the value of Qmax from the scale or recalculate it.
· Search for the concerning range in the first row of the table below.
· Read the concerning pulse rates in the second and third row.
· The measuring unit is equal to the flow

Maximum flow Qmax

without unit

Pulse rate for F34-2

without unit

Pulse rate for F34-3

without unit

Qmax ≤ 1
1 < Qmax ≤ 10
10 < Qmax ≤ 100
100 < Qmax ≤ 1000
1000 < Qmax ≤ 10000
10000 < Qmax ≤ 100000

0.0001
0.001
0.01
0.1
1
10

0.001
0.01
0.1
1
10
100

e.g..: Final value (Qmax ) = 400 m3/h

→ Pulse rate 0.1 m

3

for F34-2 and 1 m

3

for F34-3

The factory default is F34 -2 (solution : 1 last digit).

After Master Reset F34 -1 (Pulse output not active) is selected.
After changing the flow rate unit with F12 the pulse-register is deleted and the pulse rate is automatically

redefined according to the new unit.
After totalizer Reset with F14 the pulse output does not change.
When changing the indication with F11 -3 to ´%´, the totalizer stops and the pulse output is switched off.
After switching power on one pulse is generated at the output.
For 2- respectively 3-wire-units the function F34 is not supported.

NOTE