Yokogawa RAMC User Manual

Page 107

Advertising
background image

<10. EXPLOSION-PROTECTED TYPE INSTRUMENTS>

10-15

IM 01R01B02-00E-E 10th edition January 01, 2013 -00

All Rights Reserved. Copyright © 2003, Rota Yokogawa

10.7.2 Limit switches option /K1 ... /K10 (/FS1 for USA)

Data of limit switches (FM-approval):
The limit switches are intrinsically safe devices. They are certified by Pepperl & Fuchs for:
Intrinsically safe :

Cl. I, Div. 1, GP. A, B, C, D T6 Ta=60°C

Cl. II, Div. 1, GP. E, F, G

Cl. III, Div. 1


Non incendive:

Cl. I, Div. 2, GP. A, B, C, D T5 Ta=50°C

Cl. II, Div. 1, GP. E, F, G

Cl. III, Div. 1

Maximum Entity Field Wiring Parameters :

see FM-control drawing 116-0165 on page 10-16 and 10-17 for intrinsic safety

see FM-control drawing 116-0155 on page 10-18 for non incendive

10.6.3 Limit switches option /K1 ... /K3 (/CS1 for Canada)

Data of limit switches (CSA-approval):
The limit switches are intrinsically safe devices. They are certified by Pepperl & Fuchs for:
Intrinsically safe :

Cl. I, Div. 1, GP. A, B, C, D

Cl. II, Div. 1, GP. E, F, G

Cl. III, Div. 1

Maximum Entity Field Wiring Parameters :

see CSA drawing 116-0047 on page 10-19 and 10-20

WARNING

Only in combination with power supply option /WxA or /WxB.

Advertising